ake sure that the probe is not subjected to strong lateral forces.
M
ount VEGAFLEX 62 at a position in the vessel where no
disturbances, e.g. from filling openings, agitators, etc., can occur.
Fig. 11: Lateral load
I
f there is a danger of the probe touching the vessel wall during
operation due to product movements or agitators etc., the measuring
probe should be securely fixed.
I
n the gravity weight there is a thread (M12), e.g. for a ring bolt
(
optional) - (article no. 2.27424).
M
ake sure that the probe cable is not completely taut. Avoid tensile
loads on the cable.
A
void undefined cable-vessel connections, i.e. the connection must be
either grounded reliably or isolated reliably. Any deviation from this
requirement can lead to measurement errors.
Inflowing medium
Fixing
VEGAFLEX
62 • 4 … 20
mA/HART two-wire
19