VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual
Page 42
42
6 Set up with the indicating and adjustment module
VEGAPULS 62 • Profibus PA
36505-EN-121011
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
With this selection, the operating range of the sensor is adapted to
the vessel height and the reliability with different frame conditions is
increased considerably.
Independent from this, the min. adjustment must be carried out.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Since a radar sensor is a distance measuring instrument, the distance
from the sensor to the product surface is measured. For indication of
the real level, an allocation of the measured distance to the percent-
age height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
100%
0%
0,5 m (19.68
")
5 m
(196.9
")
2
1
Fig. 37: Parameter adjustment example min./max. adjustment
1 Min. level = max. meas. distance
2 Max. level = min. meas. distance
If these values are not known, an adjustment with the distances of for
example 10 % and 90 % is possible. Starting point for these distance
Setup/Vessel height,
measuring range
Setup/Adjustment