VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire User Manual

Page 66

Advertising
background image

66

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-121011

Max. output current

22 mA

Starting current

≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on

Load

see load diagram under Power supply

Damping (63 % of the input variable),

adjustable

0 … 999 s

HART output values according to HART 7.0

1)

Ʋ PV (Primary Value)

Distance to the level

Ʋ SV (Secondary Value)

Level as percentage value

Ʋ TV (Third Value)

Linearised percentage value

Ʋ QV (Fourth Value)

Scaled measured value

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Largest false echo 20 dB smaller than the useful echo

Deviation with liquids

See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

0

1 2

3

Fig. 56: Deviation under reference conditions - encapsulated antenna system
1 Reference plane

2 Antenna edge

3 Recommended measuring range

1)

Default values, can be assigned individually