5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

The following values can be displayed:

•

Height

•

Pressure (only with pressure transmitters)

•

Distance (only with radar, guided microwave, ultrasonics)

•

Current

•

Scaled

•

Percent

•

Lin. percent

•

Temperature (only with pressure transmitters).

The selection "scaled" opens the menu items "Display unit" and

"Scaling". In "Display unit" there are the following options:

•

Height

•

Ground

•

Flow

•

Volume

•

Without unit

Depending on selection, the different units are in turn available.
In the menu item "Scaling", the requested numerical value with deci-

mal point is entered for 0 % and 100 % of the measured value.
There is the following relationship between the indication value in the

menu "Display" and the adjustment unit in the menu "Device settings":

•

With radar, guided microwave and ultrasonics, the displayed value

"Distance" means: presentation of the measured value in the

selected adjustment unit, e.g. m(d)

•

With pressure, the displayed value "Pressure" or "Height" means:

presentation of the measured value in the selected adjustment

unit, e.g. bar or m.

Displayed value

Scaled

▼

Display unit

Volume

▼

l

▼

Scaling

0 % = 0.0 l
100 % = 100.0 l

In the menu item "Current output" you determine the behaviour of the

current output during operation and in case of failure. The following

options are available:

Service/Current output