6 Set up with the indicating and adjustment module
VEGAPULS 62 standpipe version • Profibus PA
36509-EN-121011
With radar sensors with standpipe antenna, the sensor length is
already preset in this menu item. When shortening the standpipe
antenna afterwards, this value must be appropriately corrected.
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
ment from the factory incl. the order-specific settings. A created false
signal suppression, user-programmable linearization curve as well as
the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and
laboratory parameters to the default values of the respective instru-
ment. A created false signal suppression, user programmable lineari-
zation curve as well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the
respective instrument in the menu item Setup. Order-related settings
remain but are not taken over into the current parameters. User-
generated false signal suppression, user-programmed linearization
curve, measured value memory as well as event memory remain
untouched. The linearization is set to linear.
False signal suppression: Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values distance: Resetting the measured min. and max. dis-
tances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 62:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Min. adjustment
Length of the standpipe Ex factory
Max. adjustment
0,000 m(d)
AI FB1 Channnel PV (lin. perc.)
AI FB1 scaling
unit
Height
%
Additional adjustments/
Probe length
Additional adjustments/
Reset