6 Set up with the display and adjustment module
VEGABAR 83 • 4 … 20 mA
45033-EN-131010
Menu item
Parameter
Default value
Position correc-
tion
0.00 bar
Adjustment
Zero/Min. adjust-
ment
0.00 bar
0.00 %
Span/Max. adjust-
ment
Nominal measuring range in bar
100.00 %
Damping
Integration time
0.0 s
Current output
Current output -
Mode
Output characteristics
4 … 20 mA
Reaction when malfunction occurs
≤ 3.6 mA
Current output -
Min./Max.
3.8 mA
20.5 mA
Lock adjustment
Released
Reset - Display
Menu item
Default value
Menu language
Order-specific
Displayed value 1
Current output in %
Displayed value 2
Measuring cell temperature in °C
Backlight
Switched off
Reset - Diagnosis
Menu item
Parameter
Default value
Sensor status
-
Peak value
Pressure
Actual measured value
Temperature
Actual temperature values from meas-
uring cell, electronics
Simulation
Process pressure
Reset - Additional settings
Menu item
Parameter
Default value
PIN
0000
Date/Time
Actual date/Actual time
Copy in-
strument
settings
Special pa-
rameters
No reset