12 2 a b – VEGA VEGAFLEX series 80 Centering User Manual
Page 15
15
2 Mounting
Centering • for VEGAFLEX series 80
44967-EN-131119
1
1
2
2
A
B
45 mm (1.77"
)
100 mm
(3.94"
)
25 mm (0.98"
)
50 mm
(1.97"
)
Fig. 12: Mounting the gravity weight (S1, S2)
A Gravity weight - cable ø 4 mm (0.16 in)
B Gravity weight - cable ø 2 mm (0.08 in)
1 Threaded pins
2 Thread M8, e.g. for eye-bolt
1. Slide the cable (according to the drawing) into the gravity weight
(A, B) up to the stop
2. Fasten the cable with the threaded pins, torque 7 Nm (5.16 lbf ft)
3. If you retrofit a gravity weight, you have to select the correct probe
type in the instrument (e.g. cable ø 4 mm with gravity weight). If
the probe length has changed, you have to enter the new probe
length in the instrument and then carry out the adjustment again
(see also "Setup steps, Carry out min. adjustment - Carry out
max. adjustment").
The following process describes the mounting of the spacer on the
gravity weight.
Mounting the spacer