3 function chart "point level – VEGA VEGATOR 111 User Manual
Page 14
14
6 Setup
VEGATOR 111 •
46105-EN-131217
is released. Please note that when line monitoring is deactivated, the
red signal lamp does not light up.
Note:
Keep in mind that downstream connected devices are activated dur-
ing the function test. This allows you to check the correct function of
the measuring system.
6.3 Function chart "Point level"
The following chart provides an overview of the switching conditions
depending on the set mode and the level.
Note:
The switching conditions in the tables are only valid if the mode
switch on the sensor is set to "Max.".
Sensor
Signal conditioning instrument
Level
Sensor
current
LED yel-
low
(output)
LED red
(failure)
Relay
Fail safe
relay (op-
tional)
approx.
2.1 mA
ON
ON
approx.
1.2 mA
OFF
ON
any
< 0.35 mA
> 6.8 mA
OFF
OFF
Sensor
Signal conditioning instrument
Level
Sensor
current
LED yel-
low
(output)
LED red
(failure)
Relay
Fail safe
relay (op-
tional)
approx.
1.2 mA
ON
ON
approx.
2.1 mA
OFF
ON
any
< 0.35 mA
> 6,8 mA
OFF
OFF
Overfill protection, point
level
Dry run protection, point
level