If the medium has good reflective properties, VEGAPULS 61 can also
be mounted on a longer socket piece. Recommended values for
socket heights are specified in the following illustration. You must carry
out a false echo storage afterwards.
d
h
The below charts specify the max. socket piece length h depending on
the diameter d.
Socket diameter d
Socket length h
80 mm
300 mm
100 mm
400 mm
150 mm
500 mm
Socket diameter d
Socket length h
3"
11.8 in
4"
15.8 in
6"
19.7 in
Tip:
In new facilities it is useful to incline the vessel socket in the direction
of the outlet. False reflections from the vessel wall are thus reduced
and measurement all the way down to the bottom of the conical outlet
is possible.
18
VEGAPULS
61 • Approval according to LPR radio standard
4 Mounting
41714
-EN