VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire Coax probe User Manual
Page 41
41
6 Set up with the display and adjustment module
VEGAFLEX 86 • 4 … 20 mA/HART two-wire
42284-EN-130612
In menu item "Interface (2)" you define the scaling format on the
display and the scaling of the interface measured value for 0 % and
100 %.
In menu item"Current output, size" you determine which measured
value the current output refers to.
In menu item "Current output, adjustment" you can assign a respec-
tive measured value to the current output.
In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
Setup - Scaling Interface
(2)
Setup - Current output
Size
Setup - Current output,
adjustment
Setup/Current output
mode