VEGA VEGABAR 81 4 … 20 mA - Operating Instructions User Manual
Page 32
 
32
6 Set up with the display and adjustment module
VEGABAR 81 • 4 … 20 mA
45025-EN-131010
3. Set the requested mbar value with [+] and store with [OK].
4. Move with [ESC] and [->] to the span adjustment
The	zero	adjustment	is	finished.
Information:
The zero adjustment shifts the value of the span adjustment. The
span, i.e. the difference between these values, however, remains
unchanged.
For an adjustment with pressure, simply enter the actual measured 
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
Proceed as follows:
1. Select with [->]	the	menu	item	"Span	adjustment"	and	confirm	
with [OK].
2. Edit the mbar value with [OK] and set the cursor to the requested
position with [->].
3. Set the requested mbar value with [+] and store with [OK].
For an adjustment with pressure, simply enter the actual measured 
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
The	span	adjustment	is	finished.
Proceed as follows:
1. Select the menu item "Setup" with [->]	and	confirm	with	[OK]. 
Now select with [->] the menu item "Adjustment", then "Min.
adjustment"and confirm with [OK].
Setup - span adjustment
Setup - Min. adjustment
Level