6 Set up with the display and adjustment module

VEGABAR 83 • HART and accumulator pack

45035-EN-131107

In the menu items "Current output" you determine the properties of

the current output.
On instruments with a 2nd integrated current output, the properties for

each current output are adjusted individually. The following descrip-

tions apply to both current outputs.

In menu item"Current output, size" you determine which measured

value the current output refers to.

In menu item "Current output, adjustment" you can assign a respec-

tive measured value to the current output.

In the menu item "Current output mode" you determine the output

characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode

< 3.6 mA.

In the menu item "Current output Min./Max.", you determine the reac-

tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.
The following adjustment functions are possible without entering the

PIN:

Select menu items and show data

Setup - Current output

Additional settings - Cur-

rent output 1 and 2 (size)

Additional settings -

Current output 1 and 2

(adjustment)

Setup - Current output 1

and 2 (mode)

Setup - Current output 1

and 2 (min./max.)

Lock/release setup - Ad-

justment