3 Mounting

VEGABAR 83 • Profibus PA

46316-EN-131125

3 Mounting

3.1 General instructions for use of the instrument

Protect your instrument against moisture penetration through the fol-

lowing measures:

•

Use the recommended cable (see chapter "Connecting to power

supply")

•

Tighten the cable gland

•

Turn the housing in such a way that the cable gland points down-

ward

•

Loop the connection cable downward in front of the cable gland

This applies particularly to:

•

Outdoor mounting

•

Installations in areas where high humidity is expected (e.g. through

cleaning processes)

•

Installations on cooled or heated vessels

3.2 Ventilation and pressure compensation

The filter element is mounted into the electronics housing. It has the

following functions:

•

Ventilation of the electronics housing

•

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

→

Turn the housing so that the filter element points downward after

the instrument is installed. This provides better protection against

buildup.

1

2

3

4

4

4

Fig. 2: Position of the filter element - non-Ex, Ex-ia version
1 Housing plastic, stainless steel precision casting

2 Housing aluminium

3 Housing stainless steel, electropolished

4 Filter element

With the following instruments a blind plug is installed instead of the

filter element:

•

Instruments in protection IP 66/IP 68 (1 bar) - ventilation via capil-

laries in non-detachable cable

•

Instruments with absolute pressure

Protection against mois-

ture

Instruments in non-Ex

and Ex-ia version