VEGA KLD2-PL-Ex1.PA Power-Link for PROFIBUS DP-PA segment coupler SK2 User Manual

Kld2-pl-ex1.pa power-link, Composition

Advertising
background image

1

096

79

0_

EN

G.xm

l

2

003

-02-

2

7

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

KLD2-PL-Ex1.PA

Power-Link

Power rail

Power

Saf

e area

Hazar

dous area

Connection to gateway

CH 1 ... 4

PROFIBUS-PA segment

[EEx ia] IIC

+

FE

-

S

+

-

+

-

16

1

17

2

41

CH

40

42S

59

60

58

18

3

Z

Composition

Power-Link for an intrinsically safe
PROFIBUS PA segment

• PROFIBUS PA according to

EN 50170/2 and IEC 61158-2;
31,25 kbit/s

• Up to 10 Ex devices can be

connected to the PA segment

• Supply via Power Rail
• 24 V DC rated operational voltage
• Removable terminals and Power

Rail

• EMC acc. to NAMUR NE 21
• Field circuit in the hazardous area

EEx ia IIC and Class I, Division 1,
Groups A, B, C and D

Together with the KLD2-GT-DP(R).xPA
Gateway, the Power-Link forms an SK2
Segment Coupler and can only be operat-
ed in association with it. The KLD2-PL-
Ex1.PA can be installed in Zone 2. The
Power-Link thus provides the intrinsically
safe interface. The PROFIBUS PA sta-
tions are supplied from the Power-Link via
the bus.
Data exchange between the Power-Link
and channel 1 of the KLD2-GT-
DP(R).xPA gateway takes place via the
power rail. If the Power-Link is operated
with channel 2, 3 or 4 of the gateway, a
wire connection for the data exchange
must be provided between the Power-Link
and the gateway, via the removable termi-
nals.
The communication of the SK2 segment
coupler behaves transparently. The Pow-
er-Link does not have to be configured.
The baud rate of the intrinsically safe
PROFIBUS PA segment is 31.25 kbit/s,
in accordance with IEC61158-2.

Please note!
Information on the commissioning of the
Profibus PA can be obtained from the
guidance documentation of the PROFI-
BUS User Organisation.

Function

Power-Link for PROFIBUS DP/PA segment coupler SK2