Altronix Maximal77 Installation Instructions User Manual
Page 8

- 8 -
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
Power Supply Board Stand-by Battery Specifications:
Altronix
Model
Power Supply Board
Battery
20 Min. of
Backup
4 Hr. of Backup
24 Hr. of Backup
Maximal11
AL400ULXB
(Refer to Fig. 1a, pg. 9
for Switch [SW1]
location and position)
12VDC/40AH*
N/A
3.5 amp
0.5 amp
24VDC/40AH*
N/A
2.7 amp
0.7 amp
Maximal33
AL600ULXB
(Refer to Fig. 1a, pg. 9
for Switch [SW1]
location and position)
12VDC/40AH*
N/A
5.5 amp
5.5 amp
24VDC/40AH*
N/A
5.5 amp
0.7 amp
Maximal55
Maximal75
AL1012ULXB
(Factory set at 12VDC)
12VDC/12AH
9.0 amp
Battery capacity for
emergency stand-by
at least 20 min
N/A
Maximal75
AL1024ULXB
(Factory set at 24VDC)
24VDC/12AH
7.7 amp
1.2 amp
N/A
Maximal77
AL1024ULXB
(Factory set at 24VDC)
24VDC/65AH*
N/A
7.7 amp
1.2 amp
* Note: Additional battery enclosure required (Figs. 6-9, pg, 14-17)