Wiring distance table: typical application diagram – Altronix StrikeIt2 Installation Instructions User Manual
Page 5
Advertising

StrikeIt2
- 5 -
--- OUT
+
AC LED
UNLOCK
L G N
GND NO -- BAT + -- Aux +
Trg
Panic Hardware Device
24VDC
REX PIR
Access
Control
Panel
+
---
Rechargeable
Batteries
12VDC
+
---
12VDC
115VAC power mains
non power-limited
6.3A
250V
Fig. 1
Wiring Distance Table:
Typical Application Diagram:
InRush
Current
Wire Gauge
Electric Butt or Pivot
Max distance from Power Supply to frame side of opening
EPT
Max distance from Power Supply to frame side of opening
8 amp
14 AWG Stranded
75 ft.
100 ft.
8 amp
12 AWG Stranded
175 ft.
200 ft.
12 amp
14 AWG Stranded
60 ft.
75 ft.
12 amp
12 AWG Stranded
80 ft.
100 ft.
16 amp
14 AWG Stranded
40 ft.
75 ft.
16 amp
12 AWG Stranded
60 ft.
80 ft.