Page 6: Normal operating condition, Loss of ac, stand-by battery supplying power, No dc output. loss of ac. discharged battery, Fig. 1
Advertising
- 6 -
Maximal Expandable Power Systems
NO NC C NO
+
B
A
T
-
--
24V - OPEN
12V - CLOSED
AC FAIL
RL3
SW1
AC Delay
BAT FAIL NC C NO NC C NO
+
B
A
T
---
DC
AC FAIL
AC
24V - OPEN
12V - CLOSED
SW1
Fig. 1a
AL400ULXB Power Supply Board
Fig. 1c
AL600ULXB Power Supply Board
Fig. 1b
OPEN SWITCH
CLOSED SWITCH
Switch Detail
Power Supply Board LED Diagnostics:
LED
Power Supply Status
Red (DC) Green (AC)
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged battery
Power Supply Board Output Voltage Settings: