Altronix R1224DC16CB Installation Instructions User Manual

Page 2

Advertising
background image

- 2 -

R1224DC16CB

Overview:

These Altronix Rack Mount Power Supplies provide 12VDC or 24VDC distributed via sixteen (16) PTC protected
Class 2 Rated outputs for power limited installation.

Rack Mount Configuration Reference Chart:

Altronix

Model Number

Output Voltage

Total Output Current (Power)

Number of Ouputs

Class 2 Rated Power Limited Outputs

PTC Protected Outputs

Output Current (max per output)

115VAC 60Hz Input Current

Agency Listing

R1224DC16CB

12VDC

18 amp

16

3

3

2

amp

3.74 amp

Specialty Power Supply

UL1012

CUL Listed - CSA Standard

C22.2 No.107.1

24VDC

18 amp

6.26 amp

Specifications:

Caution: This installation should be made by qualified service personnel and should conform to all local

codes and the National Electrical Code.

Installation Instructions:

1. Attach mounting brackets to unit for rack mount installation (Fig. 1a, pg. 3). Affix rubber pads to unit

for shelf installation (Fig. 2, pg. 3).

2. Secure the unit in a rack or place unit on a shelf as desired (unit should be spaced at least 3” from any video

monitors). When installing the unit in a rack allow for one half of a U spacing above the unit for ventilation.

3. Insert and secure removable terminal blocks to unit (Fig. 3c, pg. 4).
4. Plug the grounded AC line cord (included) into the IEC 320 connector of the R1224DC16CB unit (Fig. 3a, pg. 4).

Insert the plug end of the line cord into a grounded AC receptacle.

5. Select 12VDC or 24VDC power for each group of four (4) outputs 1a - 1d through 4a-4d with the corresponding

voltage selector switches (Fig. 3b, pg. 4).

Note: Each voltage selector switch sets the voltage for the entie group of four (4) corresponding outputs.

6. Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3d, pg. 4).
7. Measure output voltage before connecting devices. This helps avoid potential damage.
8. Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3d, pg. 4).
9. Connect the power output of terminals marked [+ 1A -- ] to the power inputs of device (Fig. 3c, pg. 4).

Repeat this step for the other remaining power outputs.

10. Upon completion of wiring, set illuminated master power disconnect circuit breaker to the

ON (RESET) position (Fig. 3d, pg. 4).

11. All four (4) power LEDs on the faceplate will illuminate when AC power is present (Fig. 1a, pg. 4).

Note: If the power LEDs are not illuminated the cause may be due to the following:

a. AC mains fail.

b. Illuminated master power disconnect circuit breaker is OFF or tripped.

If one (1) or more power output PTCs are tripped due to a short circuit or overload condition follow the steps

below to reset PTC:

• 115VAC 60Hz input.
• Sixteen (16) PTC protected outputs.
• 18 amp total (current 12 amp max. per output)
• Power LED indicators per group of 4 outputs.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.

• Illuminated power disconnect circuit breaker with
manual reset.
• Removable terminal blocks w/locking screw flange.
• IEC 320 - 3-wire grounded line cord (detachable).
• 3U rack mount chassis for use in standard EIA 19” rack.
• Ease of installation saves time and eliminates
costly labor.