Terminal Indentification:
Terminal
Function/Description
Legend
AC / AC
Low voltage AC input (24VAC / 40VA min.). Altronix part # TP2440.
+ DC -
24VDC 750 mA continuous power limited output.
AC FAIL
Used to notify loss of AC power, e.g. connect to audible device or alarm
NC, C, NO
panel. Relay normally energized when AC power is present.
Contact rating 2 amps @ 120VAC / 28VDC
Low Battery
Used to indicate low battery condition, e.g. connect to alarm panel.
NC, C, NO
Relay normally energized when DC power is present.
Contact rating 2 amps @ 120VAC / 28VDC
- BAT +
Stand-by battery connections. Maximum charge rate 200mA.