Terminal identification, Maximum input voltage not to exceed 28vac – Altronix SMP3PM Installation Instructions User Manual

Page 2

Advertising
background image

- 2 -

SMP3PM

Terminal Identification:

Terminal Legend Function/Description

AC/AC

Low voltage AC input (Voltage Output/Transformer Selection Table).
For 12VDC output use 16VAC or higher with 24VA power rating or higher.
For 24VDC output use 28VAC with 85VA power rating or higher.
Caution: Do not apply voltages above 28VAC (28VAC is maximum input rating

+ DC --

12VDC/24VDC @ 2.5 amp continuous output.

AC FAIL

NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm
NC, C, NO panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 120VAC / 28VDC

Low Battery

NC, NO,

Used to indicate low battery condition, e.g. connect to alarm panel.
NC, NO, C Relay normally energized when DC power is present.
Contact rating 1 amp @ 120VAC / 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.

+ BAT -

Stand-by battery connections. Maximum charge rate 0.3 amp.

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Made in U.S.A.
IISMP3PM - Rev. 090710

B09L

+ BAT --- + DC ---

AC

AC

DC

AC

SUPERVISED POWER

SUPPLY/CHARGER

12V - SW1 CLOSED

24V - SW1 OPEN

AC FAIL

LOW BAT

NC

C

NO

C

NC
NO

Maximum input

voltage not to

exceed 28VAC