Terminal Identification:
Terminal Legend
Function/Description
L, G, N
Connect 115VAC to these terminals:
L to Hot, N to Neutral, G to ground.
– DC +
12VDC @ 10 amp continuous supply current.
AC FAIL
NC, C, NO
Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp @ 28VDC.
Low Battery
NC, C, NO
Used to indicate low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present.
Contact rating 1 amp @ 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
– BAT +
Stand-by battery connections. Maximum charge rate 0.7 amp.