Altronix SMP3PMP8CB Installation Instructions User Manual

Page 2

Advertising
background image

- 2 -

SMP3CTXseries

3. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G] (if used).

Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).

4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered:

a. For Power Supply Board connect to terminals marked [– DC +].
b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked
[1P & 1N thru 4P & 4N] (Fig. 2, pg. 3), 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3, pg. 3), or 1 to 16 marked
[1P & 1N thru 16P & 16N] (Fig. 4, pg. 3) carefully observing correct polarity.
*Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit,
AC mains should be removed.

6. When using stand-by batteries, they must be lead acid or gel type. Connect battery to terminals marked [– BAT +]

(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of AC will result in the loss of output voltage.

For supervised models only:
7. Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs

marked [NC, C, NO] (Fig. 1a, pg. 3).

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal

Function/Description

Legend

L, G, N

Connect 115VAC/230VAC to these terminals:
L to Hot, N to Neutral, G to ground (if used).

– DC +

12VDC / 24VDC @ 2.5 amp continuous non-power limited output.

*AC FAIL

Indicates loss of AC power, e.g. connect to audible device or alarm

NC, C, NO

panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 120VAC / 28VDC.

*Low Battery

Indicates low battery condition, e.g. connect to alarm panel.

NC, C, NO

Relay normally energized when DC power is present.
Contact rating 1 amp @ 120VAC / 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate .5 amp.

*Note: Supervised models only

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module

Terminal Legend

Function/

PD4/PD4CB

PD8/PD8CB

PD16W/PD16WCB

Description

1P to 4P

1P to 8P

1P to16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.

Advertising