Altronix AL600ULXD Installation Instructions User Manual
Page 3

LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Statu
s
ON
ON
Normal operating condition
ON
OFF
Loss of AC, Stand-by battery supplying power
OFF
ON
No DC output
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output
Terminal Identification:
Terminal
Function/Description
Legend
AC / AC
Low voltage AC input (28VAC / 200VA).
Two (2) Altronix part # T2885D.
+ DC -
12VDC / 24VDC @ 6 amp continuous non-power limited output.
AC FAIL
Used to notify loss of AC power, e.g. connect to audible device or alarm
C, N.C., N.O.
panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 28VDC
Low Battery
Used to indicate low battery condition, e.g. connect to alarm panel.
N.O., N.C., C
Relay normally energized when DC power is present.
Contact rating 1 amp @ 28VDC
- BAT +
Stand-by battery connections. Maximum charge rate .7 amp.