Altronix AL400UL Installation Instructions User Manual
Page 3
Advertising
AL400UL
- 3 -
LED Diagnostics:
LED
ON
OFF
AC (Green)
Normal operation
No AC input
BAT (Red)
Battery connected
Battery disconnected
DC (Red)
Normal operation
No DC output
Terminal Identification:
Terminal Legend Function/Description
AC, AC
Low voltage (28VAC) transformer connections.
-- DC +
12VDC @ 4 amp or 24VDC @ 3 amp continuous power-limited output.
AC Fail
NC, NO, C
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized
when AC power is present. Contact rating 1 amp @ 30VDC.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1 amp @ 30VDC.
-- BAT +
Stand-by battery connections. Maximum charge current 1.2 amp.