Altronix ALTV2416ULX3 Installation Instructions User Manual

Page 3

Advertising
background image

ALTV2416UL3series

- 3 -

4. Plug-in 3-wire line cord (Figs. 1, 2, pgs. 4, 5).

Keep power limited (PTC protected outputs only) wiring separate from non-power limited wiring.

Minimum .25” spacing must be provided. Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV2416ULX3 or

ALTV2416ULCBX3 (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to RESET (ON) position for

all other models (Figs. 3a-8a, pgs. 6-10).

6. Measure output voltage before connecting devices. This helps avoid potential damage.

Terminals marked [1P - 16P] are of the same polarity.

CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting

the output voltage.
7.

Set power switch on power distribution board marked [PD] to OFF position for models ALTV2416ULX3 or

ALTV2416ULCBX3 (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to OFF position for all

other models (Figs. 3a-8a, pgs. 6-10).

8. Connect devices to terminals marked [1P - 1N through 8P - 8N] on PD8 board (Figs. 1-4, 7, 8, pgs. 4-7, 9, 10),

or terminals marked [1P - 1N through 16P - 16N] on PD16W/PD16WCB board (Fig. 5, pg. 8), carefully

observing polarity.

9. Set power switch on power distribution board marked [PD] to ON position for models ALTV2416ULX3 or

ALTV2416ULCBX3 (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to RESET (ON) position for

all other models (Figs. 3a-8a, pgs. 6-10).

10. Green LED will illuminate when power is present.
11. Upon completion of wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional.
Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes
and in accordance with the National Electrical Code. Use 75º C or higher rated UL insulated wiring for
connecting the unit to the mains. Replace fuses only with the same type and rating (refer to Sixteen (16)
Output ALTV2416UL3 Reference Chart, pg. 2)

Terminal Identification:

PD8 - Power Distribution Module

Terminal Legend

Function/Description

1P - 8P

AC output.

1N - 8N

AC output.

PD16W - Power Distribution Module

Terminal Legend

Function/Description

1P - 16P

AC output.

1N - 16N

AC output.