Altronix AL1002ULADAJ Installation Instructions User Manual
Page 5

AL1002ULADAJ
- 5 -
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification
appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate.
Amount of Notification Appliances per unit:
Amseco
27 per NAC*
System Sensor®
32 per NAC*
Faraday
39 per NAC*
CooperWheelock®
32 per NAC*
Gentex®
32 per NAC*
*Not to exceed a maximum of 2.5 amp per NAC.
Terminal Identification Table:
AL800LGK Logic Board
Terminal
Legend
Function/Description
IN1+, IN1-
IN2+, IN2-
(Supervised)
These terminals connect to the 12VDC or 24VDC FACP notification appliance circuit outputs.
(Class A, Style Z or Class B, Style W, Y) Input trigger voltage is 8-33VDC @ 5mA min. Terminal
polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected
outputs chosen to drive notification appliances. The designated outputs are set by output switches
[OUT1 through OUT4] (Output Programming Selection Table, pg. 4). A trouble condition on an
output loop will cause the corresponding input to trip the FACP by opening the FACP loop.
An alarm condition will always override trouble to drive notification appliances.
RET1+, RET1-
RET2+, RET2-
(Supervised)
For (Class A, Style Z hookups these terminal pairs return to FACP NAC1 and/or NAC2.
For Class B, Style W, Y hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs
are terminated at these terminals.
C “DRY1” NC
C “DRY2” NC
(Dry input trigger)
An open across these inputs, will cause the selected outputs chosen to drive
notification appliances. The designated outputs are set by output switches [OUT1 through OUT4]
(Output Programming Selection Table, pg. 4). Note these inputs are unidirectional and will not
report a trouble condition to the FACP.
+ OUT1 --
+ OUT2 --
+ OUT3 --
+ OUT4 --
(Supervised)
Notification appliances are connected to these regulated outputs (see Application Guide pg. 2-4).
Each power-limited output will supply 2.5 amp. Total supply current is 10 amp (see note below).
Outputs are controlled by designated input 1 [IN1] or input 2 [IN2] (Output Programming
Selection Table, pg. 4). Maximum line loss or voltage drop (tested with 2.5V).
C “FAULT” NC
(Common
trouble input)
An open circuit across this pair of terminals will cause [IN1 and IN2] to simultaneously
signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail).
(form “C” contact 1 amp / 28VDC) (Fig. 2, pg. 7).
NC, C, NO
(Common
trouble input)
These are dry contact trouble outputs that follow any general loop/system trouble conditions.
(Typically used to trigger a digital communicator or other reporting device).
(form “C” contact 1 amp / 28VDC 0.35 Power Factor) (Fig. 2, pg. 7) .
-- AUX+
This separate 1 amp max auxiliary Special Application Power output circuit is typically used to
power 4-wire smoke detectors. See attached list of devices (Appendix A, pgs. 10-12).
+ DC --
24VDC from power supply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When
loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total
alarm current (example: AUX = 1 amp, outputs up to 9 amp).