[2] load LED: indicates that the connected load receives power. When on, the load
receives enough power to operate normally.

o

[3] battery status.
ƒ Red: the battery is empty and the controller will be in over-discharge protection

(10.5V-11V for 12V system/ 21V-22V for 24V system)

ƒ Orange: normal working status
ƒ Green: the battery is fully charged and the controller is into over-charge protection

(13.7V-14.4V for 12V system / 27.4V-28.8V for 24V system)

8.

Troubleshooting

Problem: load indicator [2] off and load stops working.

Reason: low battery voltage (battery status [3] is red).

Possible solutions:

• Remove load and press the RESET button. When battery is fully charged, reconnect

the load.

• Increase the number of solar panels or change the battery to match the connected

load.

Problem: load indicator [2] off and load stops working.
Reason: system overloaded / short circuit inside the load

Possible solutions:

• remove as much load as necessary and press the RESET button.

• resolve the short circuit problem on the load and press the RESET button.

Problem: charge indicator [1] is continuously on.
Reason: battery is charging.

Possible solutions: this is a normal operating condition.
Problem: charge indicator [1] is blinking.
Reason: battery is trickle-charging.

Possible solutions: this is a normal operating condition when battery is fully charged.
Problem: charge indicator [1] is off.

Reason: no power from solar panels.

Possible solutions:

• This is a normal condition during night time when the solar panel doesn’t receive any

sunlight

• When it happens during day-time, carefully check all connections and make sure they

are all secured tightly.

9.

Technical Specification

rated voltage

12Vdc / 24Vdc (auto-detection)

load current (max.)

10A

overvoltage protection

20Vdc / 40Vdc

over-charge protection

13.7V/27.4V

over-discharge protection

10.5V/21V

temperature compensation

-3mv/°C/cell

no load loss

max.10mA

max. cable section

2.5mm²

operating temperature

-25°C - 55°C

solar panel input voltage

12V system max.20V/24V system max.40V

dimensions

135 x 98 x 36mm

weight 182g