Differential thermostat – Velleman VMB1TSW User Manual

Page 21

Advertising
background image

DIFFERENTIAL THERMOSTAT


Using two sensors, a differential thermostat can be created. When the temperature difference between both sensors
crosses a preset value, a relay channel can be activated.
To achieve this, the first sensors must know the address of the second one. The second sensor must than be linked
to a relay channel. The temperature difference value is set on the first sensor.
The settings can be done via a temperature controller VMB1TC / VMB1TCW(W) or via the Velbus link program.


Schematic overview differential thermostat (sensor2 in heating mode):

SENSOR1

SENSOR2

t1

Set-up:

t2

Set-up:

Differential sensor address =
address sensor2

heating

Temp. Difference

∆t = -10°...10°













heating on when t1+

∆t > t2

Measured temp t1 +

∆t

= Desired temperature for sensor2
Remark:
if t1+

∆t > t

mode2

than desired temp. sensor2 = t

mode2

(mode2 = anti-freeze, night, day or comfort)



Schematic overview differential thermostat (sensor2 in cooling mode):

SENSOR1

SENSOR2

t1

Set-up:

t2

Set-up:

Differential sensor address =
address sensor2

cooling

Temp. Difference

∆t = -10°...10°












Cooler on when t1+

∆t < t2

Measured temp t1 +

∆t

= Desired temperature for sensor2
Remark: if t1+

∆t < t

mode2

than desired temp. sensor2 =

t

mode2

(mode2 = anti-freeze, night, day or comfort)


Refer to some applications of a differential thermostat below.

Advertising