Rainbow Electronics MAX1541 User Manual

Page 41

Advertising
background image

A reasonable minimum value for h is 1.5, but adjusting
this up or down allows trade-offs between V

SAG

, output

capacitance, and minimum operating voltage. For a
given value of h, the minimum operating voltage can be
calculated as:

where V

DROP1

is the parasitic voltage drop in the

charge path (see the On-Time One-Shot section),
t

OFF(MIN)

is from the Electrical Characteristics, and K is

taken from Table 3. The absolute minimum input voltage
is calculated with h = 1.

If the calculated V

IN(MIN)

is greater than the required

minimum input voltage, then operating frequency must
be reduced or output capacitance added to obtain an
acceptable V

SAG

. If operation near dropout is anticipat-

ed, calculate V

SAG

to be sure of adequate transient

response.

Dropout Design Example

V

OUT2

= 2.5V

f

SW

= 355kHz

K = 3.0µs, worst-case K

MIN

= 3.3µs

t

OFF(MIN)

= 500ns

V

DROP1

= 100mV

h = 1.5

Calculating again with h = 1 and the typical K-factor
value (K = 3.3µs) gives the absolute limit of dropout:

Therefore, V

IN

must be greater than 3.06V, even with

very large output capacitance, and a practical input volt-
age with reasonable output capacitance would be 3.47V.

Multi-Output Voltage Settings

(MAX1541 OUT1 Only)

While the main MAX1541 controller (OUT1) is optimized
to work with applications that require two dynamic out-

put voltages, it can produce three or more output volt-
ages if required by using discrete logic or a DAC.

Figure 15 shows an application circuit providing four
voltage levels using discrete logic. Switching resistors
in and out of the resistor network changes the voltage
at REFIN1. An edge-detection circuit is added to gen-
erate a 1µs pulse on GATE to trigger the fault blanking
and forced-PWM operation. When using PWM mode
(SKIP = V

CC

or open) on the main controller, the edge-

detection circuit is only required if fault blanking is
enabled. Otherwise, leave OD unconnected.

Active Bus Termination

(MAX1541 OUT1 Only)

Active-bus-termination power supplies generate a volt-
age rail that tracks a set reference. They are required to
source and sink current. DDR memory architecture
requires active bus termination. In DDR memory archi-
tecture, the termination voltage is set at exactly half the
memory supply voltage. Configure the main MAX1541
controller (OUT1) to generate the termination voltage
using a resistive voltage-divider at REFIN1. In such an
application, the main MAX1541 controller (OUT1) must
be kept in PWM mode (SKIP = V

CC

or open) in order

for it to source and sink current. Figure 16 shows the
main MAX1541 controller configured as a DDR termina-
tion regulator. Connect GATE and FBLANK to GND
when unused.

V

V

V

ns

s

V

IN(MIN)

-

=

+

×







=

.

.

.

.

2 5

0 1

1

1 500

3 3

3 06

µ

V

V

V

ns

s

V

IN(MIN)

-

=

+

×







=

.

.

.

.

.

2 5

0 1

1

1 5 500

3 0

3 47

µ

V

V

V

h

t

K

IN(MIN)

OUT

DROP1

OFF(MIN)

-

=

+

×







1

MAX1540/MAX1541

Dual Step-Down Controllers with Saturation

Protection, Dynamic Output, and Linear Regulator

______________________________________________________________________________________

41

Figure 15. Multi-Output Voltage Settings

MAX1541

REF

REFIN1

GND

GATE

R4

R3

A

C1

R2

R1

B

1000pF

1.5k

1000pF

1.5k

Advertising