Setup and Connections
Vlinx MESP211 Modbus Gateway
36
IP address, the Modbus ID, the Modbus function code, or any combination of
the three. Up to five different priorities can be set.
d. IP Address – Used to set a static Internet protocol address for the Modbus
Gateway.
e. Modbus ID – Valid range is from 1 to 247.
f. Function Code – Valid range is from 1 to 99.
Save settings by clicking the “Save” button.
CONFIGURING WITH THE WEB INTERFACE
MESP211 Modbus Gateways can be configured over the network using a standard web
browser such as Internet Explorer or Firefox.
To open the web configuration interface:
1. On a PC connected to the network, open a web browser.
Open Web Browser
Figure 37.
2. In the browser’s address bar, type the IP address of the Modbus Gateway.