Ront, Ide and, Lements – B&B Electronics NTPS-48-5 - Datasheet User Manual

Page 8: Erminals and, Iring

Advertising
background image

CS10.481

CSeries

48V, 5A, S

INGLE

P

HASE

I

NPUT

Nov. 2006 / Rev.1.1 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

www.pulspower.com Phone +49 89 9278 0 Germany

8/20

12. F

RONT

S

IDE AND

U

SER

E

LEMENTS

Fig. 12-1 Front side

Output voltage potentiometer
Open the flap to tune the output voltage.
Factory set: 48.0V

Output Terminals
Screw terminals

+ Positive output
- Negative (return) output
Dual pins per pole







Input Terminals
Screw terminals

N … Neutral input
L … Line (hot) input

... PE (Protective Earth) input

DC-on lamp (green)

On when the voltage on the output
terminals is > 37V

13. T

ERMINALS AND

W

IRING

Type

Screw

terminals

Solid

wire

0.5-6mm

2

Stranded

wire

0.5-4mm

2

American wire gauge

20-10 AWG

Ferrules

allowed, but not required

Wire stripping length

7mm / 0.275inch

Screwdriver

3.5mm

slotted or Pozidrive No 2

Recommended tightening torque

0.8Nm, 7lb.in

Instructions:

a)

Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.

b)

Follow national installation codes and installation regulations!

c)

Ensure that all strands of a stranded wire enter the terminal connection!

d)

Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).

e)

Do not use the unit without PE connection.

Advertising