Getting Started
for I-7000 Series Modules
Date: Jan-08, 2002 Version 1.02 page: 30
Figure 3-1-8. Declaration files have been added into this project.
Put a “
CommandButton
” control on “
Form1
” of this program. Add the
following codes in the sub routine “
Command1_Click()
“ :
Private Sub Command1_Click()
Dim wt As Integer
Port = 2
Open_Com Port, 9600, 8, 0, 0
SendTo7000 = "$01M"
ReceiveFrom7000 = Space(100)
Send_Receive_Cmd Port, SendTo7000, ReceiveFrom7000, 100, 0, wt
Command1.Caption = ReceiveFrom7000
Close_Com Port
End Sub
Run the program and click on the “
Command1
” button. The caption of the
“
Command1
” button will be changed to “!01xxxx”. The “!” is “OK”. The “01”
means “address at 0x01”. The “xxxx” is the module-ID. Refer to Figure 3-1-
9.
Figure 3-1-9. The module returns “!01xxxx”.