Rtd input, 6 rtd, Input – B&B Electronics DUALCON-3 - Datasheet User Manual
Page 11: 6 rtd input

DUALCON-3 USERS GUIDE
4.1.6 RTD Input
Select the range from the table below and set Switch S1 to the required values.
Range in °C
1
2
3
4
5
6
7
8
9
10 11 12
0 to 100
0
0
0
0
0
0
1
0
0
0 to 200
0
0
0
1
0 to 400
0
0
1
0
0 to 800
0
0
1
1
-50 to 50
0
1
0
0
-50 to 150
0
1
0
1
-50 to 250
0
1
1
0
-50 to 350
0
1
1
1
-100 to 50
1
0
0
0
-100 to 100
1
0
0
1
-100 to 200
1
0
1
0
-100 to 400
1
0
1
1
-200 to 200
1
1
0
0
-200 to 400
1
1
0
1
-200 to 600
1
1
1
0
-200 to 800
1
1
1
1
0
0
1
0
0
RTD linearisation ON
0
PT100
0
RTD linearisation off
1
PT1000
1
RTD 2 or 4 wire 0
RTD 3 wire 1
Switch S1
And then select the required setting from the table below for switch S2
RTD
1
2
3
4
5
6
7
8
9
10 11 12
2 Wire RTD
0
1
0
0
1
0
0
1
0
0
0
1
3 Wire RTD
0
1
0
0
0
0
0
0
1
0
0
1
4 Wire RTD
0
1
0
0
0
0
0
1
0
1
0
0
Switch S2
Please note that PC Software is available to provide information on
switch settings for your input and output requirements.
! WARNING !
DO NOT OPEN UNIT OR ADJUST SWITCHES WITH
POWER SUPPLY, INPUT OR OUTPUT CONNECTED
!
IIG-010901 Page