GW-7552 PROFIBUS/MODBUS GATEWAY User Manual (Version 1.40, Apr/2012) PAGE: 35

●

Max. I/O modules:32 modules

●

System setting module:3 byte out

●

Output module:Output Relay/Coil => 1~32 Bytes

Output Register => 1~64 Words

●

Input module:Input Relay/Coil => 1~32 Bytes

Input Register => 1~64 Words

●

Max. length of I/O data:259 Bytes

●

Output length:0~131 Bytes

●

Input length:0~128 Bytes

The modules have module parameters about the communication settings. The
module parameters are shown in the below:

A. Output Relay/Coil module parameters:

●

Modbus Slave Device ID(M):0~247

●

Start Address(M):0~65535

●

NO. of Relay/Coil(M):8*(n-1)+1 ~ 8*n Bits

n=Module size/Byte

B. Output Register module parameters:

●

Modbus Slave Device ID (M):0~247

●

Start Address(M):0~65535

●

Change Word Order:Enable/Disable (Even module only)

C. Input Relay/Coil module parameters:

●

Modbus Slave Device ID (M):0~247

●

Start Address(M):0~65535

●

NO. of Relay/Coil(M):8*(n-1)+1 ~ 8*n Bits

●

Module Type(M):Read DI/DO

n=Module size/Byte

D. Input Register module parameters:

●

Modbus Slave Device ID (M):0~247

●

Start Address(M):0~65535

●

Module Type(M):Read AI/AO

●

Change Word Order:Enable/Disable (Even module only)


Example 1:
If the user wants to read a Modbus digital input module (DI module), Device ID is
1, data address is 10010~10019, and data count is 10.