Using general commands, Pm designer operation manual – B&B Electronics WOP-2121V-N4AE - Manual User Manual
Page 106

4
3
PM Designer Operation Manual
3-45
CHAPTER 3 CREATING PANEL APPLICATIONS
3.6.7. Using General Commands
This section describes how to use the general commands provided by the type A command block. To issue a general
command, specify necessary parameters in the parameter registers and then turn on command flag #15 in Command Flag
Register.
You can request the panel to perform the following file operations using the general command and the default filename:
Operation
Parameter One Register
(Operation code)
Parameter Two
Register (Data ID)
Default Filename Format
Save logged data to
TXT file
1
ID of the data logger
(0~15)
DL<ID>_<Date>_<Time>.txt
Save logged alarms to
TXT file
2
(Not required)
AL_<Date>_<Time>.txt
Save alarm counts to
TXT file
3
(Not required)
AC_<Date>_<Time>.txt
Save recipe data to
TXT file
4
ID of the recipe block
(0~15)
RB<ID>.txt
Save recipe data to
DAT file
5
ID of the recipe block
(0~15)
RB<ID>.dat
Print screen to BMP
file (256 colors)
6
Number of the screen
S<ID>_<Date>_<Time>.bmp
Print screen to BMP
file (64K colors)
7
Number of the screen
S<ID>_<Date>_<Time>.bmp
Save logged
operations to TXT file
9
(Not required)
OL_<Date>_<Time>.txt
Save logged data to
LDF file
10
ID of the data logger
(0~15)
DL<ID>_<Date>_<Time>.ldf
Take picture and save
it to BMP file
12
ID of the USB camera
(0~3)
CAM<ID>_<Date>_<Time>.bmp
Take picture and save
it to JPG file
13
ID of the USB camera
(0~3)
CAM<ID>_<Date>_<Time>.jpg
Note for default filename format:
<ID>: ID of the data logger, ID of the recipe block, ID of the USB camera, or number of the screen
<Date>: date when saving the data; format is YYMMDD
<Time>: time when saving the data; format is hhmmss