Littelfuse M2600 Series User Manual

M2600 series, Engine control, Advanced description

Advertising
background image

Engine Control

© 2013 Littelfuse Protection Relays & Controls

Advanced

Description

The M2600 Shutdown Unit is a back-up protection device

designed for marine engines. It is ensuring safety shutdown

of the engine in case normal primary shutdown fails. Together

with Engine controller units M2000 or M2500 or other

engine controllers it can be used to build a complete control,

alarm and safety system for marine engines. Alternatively

it can work as a standalone primary shutdown unit in

applications where shutdown functionality is not included

in the start/stop device of the engine. The M2600 design is

based entirely on discreet logic, thus meeting requirements

to safety shutdown devices from the marine classification

societies.
All inputs and outputs of the M2600 have corresponding LED

indication clearly showing whether they are active or not.

The unit furnishes 10 digital shutdown inputs. One is pre-

defined for overspeed and another for emergency stop. All

inputs are dry contacts. Output relays are provided for control

of the fuel valve and the stop solenoid when stopping the

engine in normal conditions. Another output relay is provided

for emergency shutdown. Additionally the unit provides an

output for circuit breaker trip for use with gen-sets. Engine

speed (rpm) can be detected from magnetic and inductive

pick-ups connected to dedicated inputs. Alternatively the

speed can be detected from digital inputs. M2600 provides

cable monitoring on all sensor inputs and for the shutdown

relay output. Configuration is made solely with the dip-

switches and rotary switches on the unit.

Ordering Information

Simplified Circuit Diagram

Features & Benefits

www.littelfuse.com/m2600

M2600 SerieS

Shutdown Unit

Ordering nuMber

requireMent

M2600.0010

Optional

Specifications

Operating Temp.

–15°C to +70°C

Humidity

95%

Vibration

DNV vibrations class B

EMC

IEC 60945

Enclosure

IP30

Primary Supply

+24 Vdc (-30 %/+30 %) <3 W

Backup Supply

+24 Vdc (-30 %/+30 %) <3 W

Connection

Screw terminals

Type

Magnetic (2-wire), NPN and PNP (3-wire)

Rated Frequency

25.0-25,000 Hz

9 Digital Sensor Inputs Normally open contacts to COM (default) or

normally closed contacts to COM.

Optional cable monitoring.

All Relays

except where otherwise specified

Relay Response Time 20 ms (worst case)

Contact set(s)

1 normally open

Contact rating

AC: 1 A, 250 Vac; DC: 1 A, 35 Vac

Run/ Stop Solenoid relay

Relay Response Time 20 ms (worst case)

Contact Set(s)

1 normally open

Contact rating:

AC: 8 A, 250 Vac; DC: 8 A, 35 Vdc

System fault output relay (Siren)

Relay response time 20 ms (worst case)

Contact set(s)

1 change over

Contact rating:

AC: 1 A, 250 Vac; DC: 1 A, 35 Vdc

Dimensions

H 157 mm (6.2”); W 210 mm (8.3”);

D 52 mm (2.0”)

FeAtureS

beneFitS

10 digital shutdown inputs

with cable monitoring

Monitoring of e.g. oil pressure, coolant

temperature and engine speed

Speed detection

via magnetic or

inductive pick-up

No tacho relay required

LEDs for status indication

Easy overview of engine condition and

operation

Cable monitoring on

fuel valve and

stop solenoid output

Fail safe system, no need of separate cable

monitoring module

Configuration by

DIP switches

Easy installation and configuration

?

PICK-UP

RUNNING

STOP ERROR

SHUTDOWN

CABLE BREAK

ALARM

PRIMARY SUPPL

Y

SECONDARY SUPPL

Y

C/B TRIP

SHUT DOWN

FUEL V

AL

VE

STOP SOLENOID

SIREN RELA

Y

INPUTS

OUTPUTS

M2600

(Shut-Down Unit)

COM

COM

OVERRIDE

SIREN RESET

SD RESET

OVERSPEED TEST

EMERGENCY STOP

COOLANT TEMP

.

LUBE OIL PRESS.

COOLANT LEVEL

FUEL OIL LEAK.

PRIMARY +24 V
PRIMARY -
SECONDARY +24 V
SECONDARY -

1

2

3

4

5

6

7 8 9

10

11

12

13

14

15

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

S1

S2

S3

S4

Rev: 4-A-050313

Advertising