Description

The SL1026 Series is a heavy-duty transient
suppresser using Gas Plasma technology. In
response to transients that exceed the device's
breakover voltage, the device changes from a very
high impedance state to a low impedance state to
conduct harmful current away from the protected
system. The SL1026 is designed to protect electrical
and electronic equipment such as communications,
control and railway systems. Carefully designed
geometry ensures against short circuiting if a failure
occurs due to conditions and events beyond the
design criteria. Optional electrical mounting clip (part
SL1053 ) is available to aid mounting and connection.

Features

• RoHS compliant

• 55 kA surge capability

(single shot) tested with
8/20μS pulse as defined
by IEC 61000-4-5

• 40 kA surge capability

(repetitive)

• Will protect against

Trapezoidal waveforms
as specified in RIA 12.

• Will protect against

capacitor discharge
voltage transient
waveforms as specified
in RIA 12.

• Will protect against

double exponential
voltage transient
waveforms as specified
in IEC 571.

Applications

• Signaling equipment.

• Communication

equipment

• Control gear.

• Trackside cabinets.

• Cell phone base

stations

SL1026 Series

3 Electrode GDT Graphical Symbol

AGENCY

AGENCY FILE NUMBER

®

E128662

Agency Approvals

a

e

b

a = TIP

b = RING

e = GROUND

(centre electrode)

®

Electrical Characteristics

Part Number*

DC Voltage

100 V/sec

DC

Voltage

1kV/μs

1

AC

Current

9 cycles

@50-60Hz

(Amps)

1

AC

Current

50Hz

1 sec x10

(Amps)

1

Surge

Current

8/20μSec

x 10

(kAmps)

1,2

Max

Single

Surge

8/20μSec

(kAmps)

1

Max Single

Surge

10/350μSec

(kAmps)

1

150(+) and 150(-)

10/1000μSec

(Amps)

MIN

MAX

SL1026-275

200

350

800

200

10

20

40

8

200

SL1026-400

300

500

900

200

10

20

40

8

200

SL1026-700

560

840

1300

200

10

20

40

8

200

NOTES:
End of life limits
-- DC: 50% of minimum initial DC breakdown voltage limit to 150% of maximum initial
DC breakdown voltage limit.
-- Impulse: less that 150% of initial impulse breakdown voltage limit.
1. Total current through center electrode, tested using SL1053B-NL holder
2. Exceeds capability of SL1053B-NL holder

Advertising