Littelfuse T2800 Series User Manual

T2800 series, Protection relays & controls, Protection relays

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Protection Relays

Earth-Fault Protection–Solidly-Grounded Systems

T2800 SEriES

Earth-Fault Relay

Description

The T2800 Earth Fault Relay is part of the T-Line series with

modular units for protection, control and monitoring of

generators. The T2800 detects the magnitude of the current

and, if this exceeds the preset level (0.02-2 x I

N

), the pick-up

LED will indicate and the delay timer will be started. After the

preset time (0.1-10 sec.) has expired the output relay and the

corresponding LED will be activated, provided that the current

level was exceeded for the entire delay time. The T2800 has

a normally energized output relay. The relay is a latching relay

which can be reset or disabled.

OrdErinG numbEr

TErminalS

i

n

1-3

2-3

T2800.00

230 V

5 A

T2800.01

450 V

400 V

5 A

T2800.02

127 V

120 V

5 A

T2800.04

24V DC+AC

5 A

T2800.05

480 V

415 V

5 A

T2800.08

230 V

1 A

Ordering Information

Simplified Circuit Diagram

Features & Benefits

Other combinations and voltages are available on request.

Specifications

Trip Level

0.02-0.2 x I

N

or 0.2-2 x I

N

Delay

0.1-1.0 sec. or 1.0-10 sec.

Max. Voltage

660 V

Voltage Range

60-110%

Consumption

Voltage 5 VA at U

N

Current 0.3 VA at I

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally energized, latching, resetable

Contact Rating

AC: 400 V, 5 A, 2000 VA

DC: 150 V, 5 A, 150 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C

Dielectric Test

2500 V

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

9

5

10

6

18
19

8

7

I x 10

N

12

1

15
16

13

LATCHING

OFF

SEC x 10

3

2

T2800

(Earth-Fault

Relay)

FEaTurES

bEnEFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfils marine class

requirement)

Visual indication of power,

pick-up, and output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply

(up to 690 Vac)

Simplifies design and installation.

No need for PTs

Wide range of combined

current and delay

settings

Enables versatile use as earth fault relay or

standard overcurrent relay. Combining more units

offers economic alternative to relays with inverse

time response.

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw- mount

& adjustment by

potentiometers

Easy installation

Littelfuse.com/t2800

Rev: 4-A-050213

Advertising