Littelfuse D0100 Series User Manual

Protection relays & controls, Installation diagram description, Specifications

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Installation Diagram

Description

The D0100/D0900 Arc-Flash relays provide a simple and cost-

effective solution for Arc-Flash monitoring. Two light sensors

can be connected directly to one relay, or optional junction

boxes allow up to 16 sensors per relay.
Light Sensors react to light and are available with 180º or 360º

detection area. Sensors are supplied with 5, 10 or 15 m of

cable and a mounting bracket. 1-2 sensors are recommended

per cubicle or drawer.

Specifications

Voltage Supply

D0100.0010: 48-220 Vdc

D0100.0020: 24 Vdc

D0900.0010: 220-250 Vac

D0900.0020: 220-250 Vac

D0900.0030: 110 Vac

Thyristor Output

250 Vac/Vdc, 8 A cont., 25 A. for 0.1s, min. load 50 mA

Sensitivity

Adjustable 2,000-24,000 lux

Number of Sensors

Max. 16 pcs. with 2 junction boxes

Response Time

Less than 1 ms

Power Consumption D0100: 4.3 W; D0900: 3.5 W

Ambient Temperature –25°C to + 70°C

EMC

EN50081-1/2 and EN50082-1/2

Dimensions

H 90 mm (3.5”); W 105 mm (4.1”); D 75 mm (3.0”)

OrDering number

COntrOl pOwer

D0100.0010

48-220 Vdc

D0100.0020

24 Vdc

D0900.0010

220-250 Vac

Ordering Information

Features

beneFits

Compact module

Fits into wide range of Arc-Flash applications

Trip time <1 ms

Limits Arc-Flash damage and risk of injury

Two optical

sensor types

Point sensors with 180° or 360° detection area

depending on specific installation

Dual sensor input Single Arc-Flash relay can monitor 2 sensors or

junction boxes

Sensor expansion

option

Junction box allows for up to 16 sensors per Arc-Flash

relay (8 sensors/box)

Adjustable light

sensitivity

Allows for operation in bright environments and

maximum sensitivity in dark environments

Service mode

Allows for system test without tripping

Features & Benefits

aCCessOries

requirement

A0033.0010 Detector cable

2 x 0.25 mm w/screen. 100 m

Optional

A0200.0010 Light Sensor 180˚; 5 m cable

Required: At least 1 sensor

per cubicle or drawer

A0200.0020 Light Sensor 180˚; 10 m cable
A0200.0030 Light Sensor 180˚; 15 m cable
A0300.0010 Light Sensor 360˚; 5 m cable
A0300.0020 Light Sensor 360˚; 10 m cable
A0300.0030 Light Sensor 360˚; 15 m cable
D0400.0010 Junction Box.

For 8 sensors, without indication

Optional

D0500.0010 Junction Box.

For 8 sensors, with indication

Optional

D1100.0010 Diode Logic Unit

Optional

Littelfuse.com/d0900

D0100 series & D0900 series

Arc-Flash Relay

A0200 (180˚)/A0300 (360˚) Light Sensors
Line-of-sight light sensor detects an arc as small

as 3 kA within a 2-m half-sphere. Available in

180˚ or 360˚; 5, 10, or 15 m cable.

D0400/D0500 Junction Box for parallel connection

of more than 2 sensors for one relay. Designed

to connect up to 8 sensors, and is available with

and without indication. Max. 2 junction boxes

can be connected to one Arc-Flash relay.

Accessories

A

Place sensors in direct line

of sight to possible arc faults,

preferably pointing down from the ceiling.

Rev: 4-A-050213

arc-Flash monitoring

Advertising