Specifications

SELCO Arc-fault Protection System

D0100 - Arc Detecting Relay DC

Voltage Supply:

24-220V DC from battery.

Triac output:

250V AC/DC, 8A cont. 25A/ 0.1sec.

Min. load current 50mA.

Signal contacts:

2 free/220V AC/DC 1A max. 50W.

Sensitivity:

1-12mA, pre-set trip 6mA/12000 lux.

Number of detectors:

Max. 16 pcs.

Response time:

Less than 1msec.

Power consumption:

4.3W.

Ambient temperature:

-25 to +70º C.


D0500 - Junction Box with indication

Power consumption:

0.6W.

Ambient temperature:

-25 to +70ºC.


D0700 - Overcurrent Relay

Voltage Supply:

48-220V DC from battery.

Current inputs:

3-phase 5A cont., 75A /1sec.

Burden:

0.5VA/input at 5A.

Current range:

1.5-3.0 x In (7.5-15A).

Response time:

20-30 mSec.

Power consumption:

2.6W.

Ambient temperature:

-5 to +55ºC.


D0900 - Arc Detecting Relay AC

Voltage Supply:

220-250V AC.

Thyristor output with stored energy:

Storage capacitor 66 µF charged to

300V DC. E=2.97Wsec. (Joule).

Life time min 30 years at 50°C.

Min. load current 50mA.

Charging time approx. 1 sec.

Discharge time approx. 1 min.

Trip coil:

230V AC.

Signal contacts:

2 free, 230V AC/DC 1A max.50W.

Sensitivity:

1-12mA, pre-set trip 6mA/12000 lux.

Number of detectors:

Max. 16 pcs.

Response time:

Less than 1 msec.

Power consumption:

3.5 W.

Ambient temperature:

-25 to +70ºC.


Environment

EMC standards:

EN50081-1/2 and EN50082-1/2.

Enclosure:

IP31.

A0200, 180 degrees

A0300, 360 degrees

Dimensions
Item no.

Dim. mm

B

H

D1

D

D

D4

D0100

105

90

75

70

60

49

D0900

105

90

75

70

60

49

D0400

72

90

—

—

58

48

D0500

72

90

—

70

58

48

D0700

105

90

—

—

60

49

D0800

72

90

75

70

58

48

Light intensity from

an arc current of min.

3kA detected inside

of the curves will trip

the breaker.