Littelfuse MPU-32 (PGR-6200) Series User Manual

Protection relays & controls, Motor protection–advanced, Motor protection unit description

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/mpu-32

Motor Protection–Advanced

MPU-32 SERIES (PGR-6200)

Motor Protection Unit

Description

The MPU-32 Motor Protection Unit is used to provide current-

and temperature-based protection, metering, and data logging

for three-phase low-voltage medium-horsepower induction

motors. This relay is ideal for retrofitting and upgrading obsolete

or aging motor protection using existing CTs. See the PMA

Family of Panel Mount Adapter Kits to replace common

obsolete relays.

Motor Protection Unit

g

Three ac-current inputs

g

Earth-leakage-CT input

g

Programmable digital input

g

24-Vdc source for digital input

g

Programmable 4-20-mA analog output

g

On-board temperature-sensor input,

g

100-

Ω

-Platinum RTD or PTC

g

Three programmable output relays

g

Local RS-232 communications, optional Network Communications

g

PC-interface software (SE-Comm-RIS)

g

4 line x 20 character backlit LCD display

g

Keypad for programming and display selection

g

4 LEDs; 1 user programmable

Current Input Module (MPU-CIM)

The MPU-CIM Current Input Module is the interface between

the MPU-32 relay and the 5-A-secondary, 1-A-secondary, and

sensitive current transformers. The MPU-CIM is ordered

separately from the MPU-32 and can be surface- or DIN-rail

mounted. Wire-clamping terminals are standard but the MPU-CTI

is available for those who require ring-tongue terminals.

ORDERING NUMBER

COMMUNICATION

MPU-32-00-00

TIA-232

MPU-32-01-00

TIA-232 & TIA-485

MPU-32-02-00

TIA-232 & DeviceNet™

MPU-32-04-00

TIA-232 & EtherNet/IP™ & Modbus

®

TCP

NOTE: One of the following is required: MPU-CIM-00-00 Current Input Module, or

MPU-CTI-RT-00 Current Input Module with ring-tonque terminals.

Ordering Information

ACCESSORIES

REQUIREMENT

Phase CTs

Required

MPS-RTD-01-00

Optional

MPS-DIF-01-00

Optional

MPU-32-SMK

Optional

CA-945

Optional

MPU-16A-Y92A-96N

Optional

1

2

1

2

Simplified Circuit Diagram

PHASE CT

PHASE CT

GF CT

PHASE CT

MPU-CIM

MPS-RTD

RTD x 8

L2

L1

MPU-32

M

(Current Input Module)

(Motor Protection Relay)

PHASE CT

PHASE CT

GF CT

PHASE CT

L2

MPS-CTU

L1

M

MPS-RTD

MPS-OPI

RTD x 8

(Control Unit)

(Temperature

Input Module)

(Temperature

Input Module)

(Operator Interface)

D

Phase Current Transformers

Phase CTs are required to detect phase

currents. For upgrade applications, existing

CTs can be used.

Ground-Fault Current Transformer

Optional zero-sequence current transformer detects

ground-fault current. Available with 5-A and 30-A

primary ratings for low-level pickup.

MPS-RTD Temperature Input Module

Optional module provides 8 inputs to connect

Pt100, Ni100, Ni120, and Cu10 RTDs.

MPS-DIF Differential Current Module

Optional motor differential protection,

compatible with core balance and summation

current transformer connections.

B

C

Accessories

A

1

2

B

C

A

Rev: 4-A-050213

Based on Manual Rev 4

Advertising