Littelfuse PGR-4300 (GFA300) Series User Manual

Protection relays & controls, Generator ground-fault relay, Description

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/pgr-4300

Generator & Single-Function Protection–Ground Fault

PGR-4300 SeRieS (GFA300)

Generator Ground-Fault Relay

ORdeRinG numbeR

cOntROl POweR

PGR-4300-12

12 Vdc

PGR-4300-24

24 Vdc

PGR-4300-120

120 Vac

Description

The PGR-4300 Generator Ground-Fault Relay provides

a simple method for detecting a ground-fault condition

on generators without the need for current transformers

(CTs). This greatly simplifies the installation. In addition,

it is compatible with both three- and four-pole transfer

switches. This relay also monitors the neutral-to-ground path

for continuity. The PGR-4300 is ideal for any generator or

application where there is not sufficient space to install CTs.

Ordering Information

Simplified Circuit Diagram

FeAtuReS

beneFitS

No CTs required

Saves space and simplifies installation

Adjustable pickup

(100 - 1200 A)

Adjustable trip setting provides a wide range of

protection and allows system coordination

Adjustable time delay

(0 - 1.0 s)

Adjustable trip delay allows quick protection and

system coordination

Output contacts

Form C ground-fault output contacts for alarming

or tripping purposes

Analog output

(0 - 1 mA)

Provides means for connecting to an optional

meter (PGA-0500) or control system

N-G continuity alarm

Monitors neutral-to-ground integrity and alarms if

ground path becomes open circuit

Passive filtering

Eliminates nuisance tripping

Features & Benefits

PGA-0500 Analog % Current Meter

Optional panel-mounted analog meter

displays ground-fault current as a

percentage of the set-point.

Accessories

AcceSSORieS

RequiRement

PGA-0500

Optional

PMA-55

Optional

PMA-60

Optional

Note: For optional conformal coating please consult factory.

Specifications

IEEE Device Numbers

Ground Fault (50G/N, 51G/N)

Input Voltage

See ordering information

Dimensions

H 75 mm (3.0”); W 55 mm (2.2”); D 115 mm (4.5”)

Trip Level Settings

100-1200 A

Trip Time Delay Settings

0-1.0 s

Contact Operating Mode

Non-fail-safe

Test Button

Local

Reset Button

Local and remote

Output Contacts

Form C

Approvals

UL Listed

Analog Output

0-1 mA

Conformally Coated

Consult factory

Warranty

5 years

Mounting

DIN, Surface (standard)

Panel (with PMA-55 or PMA-60 adapter)

PGR-4300

L2

L1

(Generator

Ground-Fault Relay)

G

Rev: 4-A-050213