Littelfuse M2000 Series User Manual

M2000 series, Engine control, Basic

Advertising
background image

Engine Control

© 2013 Littelfuse Protection Relays & Controls

Basic

M2000 SerieS

Engine Control

Ordering nuMBer

cOntrOl pOwer

M2000.0130

12 V–24 Vdc, IP54 at front.

Description

The M2000 Engine Control controls start and stop of the

engine, monitors and protects the engine during start and

operation, and simultaneously indicates the engine and alarm

status on the front of the unit. It has 9 shutdown/alarm inputs.

It is controlling the cranking, fuel valve and stop solenoid of

the engine. It is possible to configure the unit to perform up

to 6 start attempts, with user configurable crank and rest

periods. When the engine fires, cranking will be disconnected

by activating the crank disconnect input from a tacho relay or

from a direct measurement from a magnetic pick up. When

stopping the engine, a generator circuit breaker trip is available

for genset applications. A stop delay can be configured for

cooling down the engine before stop. M2000 includes cable

check of all sensor inputs. Basic configuration can be set by

dip-switches on the rear of the unit.
Extended configuration is possible using a PC. Easy installation

is ensured by means of clamping fittings, and plug-in

connection terminals. The M2000 includes an RS485 interface

enabling MODBUS RTU communication. The M2000 has been

designed and tested for use in harsh environments.

Ordering Information

Wiring Diagram

FeatureS

BeneFitS

8 Alarm/shutdown

inputs

Monitoring of e.g. oil pressure, coolant

temperature and engine speed

Cable monitoring on

sensor inputs

Fail safe system

Speed detection from

magnetic pick-up

No tacho relay required

Type-approved by marine

classification societies

Applicable in marine control and alarm systems

RS485 Modbus RTU

Communication with HMI and SCADA systems

Features & Benefits

M0500 Tacho Detector

Reads engine speed from frequency of the

generator output voltage. The reading is

converted to a square wave signal and this

signal is provided on a dedicated output.

K3452 RS232 Cable

For configuration from PC.

Accessories

acceSSOrieS

requireMent

M0500

Optional

K3452

Optional

www.littelfuse.com/m2000

Specifications

Voltage Supply

12-24 Vdc±30% (8-32 Vdc)

Consumption

Max. 180 mA

Inputs

7 normally open contacts; 1 tacho voltage;1 pick-up

Tacho Input

Square or sine wave between 0 Vdc and

supply voltage

Pick-up Input

Square or sine wave, range 2.5 Vac to 33 Vac

Tolerance, Freq. Meas. ±2%

Frequency Range

50 Hz to 10 kHz

Outputs

11 open collector outputs, max. 150 mA per channel

Siren Relay Contact

230 Vac/2 A; 30 Vdc/2 A, 30 W

Tolerance, Delays

± 2%

LED Flash Frequency Slow flashing light: 1.25 Hz ±10%

Quick Flashing Light 5 Hz ±10%

Programming

16 dip-switches or via RS232 interface

Communication

RS485 interface

Protocol

MODBUS-RTU

Baud Rate

1200, 2400, 4800, 9600

Parity

None

Data Bits

8

Stop Bits

1

Operating Temp.

–20°C to +70°C

Humidity

95% RH at 20°C

Vibration Test

4 g RMS according to IEC 60068-2-64

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Weight

0.4 kg

Dimensions

H 144 mm (5.7”); W 144 mm (5.7”); D 35 mm (1.4”)

Panel Cut-out

H 138 mm (5.4”); W 138 mm (5.4”)

Protection Degree-Front IP54 or IP32 (see Type Description)

17

27

30

31

32

29

28

16

15

4

2

3

1

INPUTS

LOCAL

START

AUTO

START

MODE

CIRCUIT

CHECK

+

24 V

M2000

ENGINE CONTROLLER

OUTPUTS

Rev: 4-A-050313