Ground-Fault Protection–Grounded Systems

Description

The SE-704 is a microprocessor-based ground-fault relay for resistance-

and solidly-grounded systems. It offers very sensitive ground-fault

detection as low as 10 mA and can be used on systems with

significant harmonic content. The SE-704 provides feeder-level

protection or individual-load protection. The output contacts can be

connected for use in protective tripping circuits or in alarm indication

circuits. The analog output can be used with a PLC or a meter.

SE-704 SEriES (PGr-4704)

Earth-Leakage Monitor

Specifications

IEEE Device Numbers

Ground fault (50G/N, 51G/N)

Input Voltage

See ordering information

Dimensions

H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")

Trip Level Settings

10 mA-5.0 A

Trip Time Settings

30-2000 ms

Contact Operating Mode Selectable fail-safe or non-fail-safe
Harmonic Filtering

Standard feature

Test Button

Standard feature

Reset Button

Standard feature

CT-Loop Monitoring

Standard feature

Output Contacts

Isolated Form A and Form B

Approvals

UL Listed (E340889), CSA, C-Tick (Australian)

Analog Output

0-5 V & 0-1 mA

Conformally coated

Consult factory

Warranty

5 years

Mounting

DIN, Surface (standard)

Panel (with PMA-55 or PMA-60 adapter)

OrdErinG numbEr

cOntrOl POwEr

SE-704-0U

120/240 Vac/Vdc

SE-704-0D

12/24 Vdc

SE-704-0T

48 Vdc

SE-704-O3

24 Vac

Ordering Information

Simplified Circuit Diagram

FEaturES

bEnEFitS

Adjustable pickup

(10 mA - 5 A)

Adjustable trip setting provides a wide range of low-level

protection and system coordination

Adjustable time delay

(30 ms - 2.0 s)

Adjustable trip delay allows quick protection and system

coordination

Output contacts

Form A and Form B ground-fault output contacts for

operation of separate annunciation and trip circuits

Analog output

(0 - 5 V)

Allows for connecting an optional meter (PGA-0500) or

control system

CT-Loop monitoring

Alarms when CT is not connected

Selectable contact

operating mode

Selectable fail-safe or non-fail-safe operating modes

allows connection to shunt or undervoltage breaker coil

Harmonic filtering

Eliminates nuisance tripping

Non-volatile trip

memory

Retains trip state when de-energized to simplify

troubleshooting

Microprocessor based No calibration required saves maintenance cost
Universal

power supply

Allows operation in application where one side of PT is

faulted, provides flexibility for numerous applications

Features & Benefits

Note: For optional conformal coating please consult factory.

accESSOriES

rEquirEmEnt

SE-CS30 Series

Required

PGA-0500

Optional

PMA-55, PMA-60

Optional

Accessories

SE-CS30 Series Ground-Fault Transformer

Required zero-sequence current transformer

specifically designed for low level detection. Flux

conditioner is included to prevent saturation.

PGA-0500 Analog % Current Meter

Optional panel-mounted analog meter displays ground-

fault current as a percentage of the set-point or 5 A.