Littelfuse T3000 Series User Manual

T3000 series, Protection relays & controls, Generator & single-function protection–frequency

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/t3000

Generator & Single-Function Protection–Frequency

T3000 SerieS

Frequency Relay

Description

The T3000 Frequency Relay is designed for frequency

monitoring on generators, bus bars or other distribution

systems.
The T3000 consists of two circuits, one circuit for over

frequency and one for under frequency monitoring. Each

circuit has individual settings for frequency levels and time

delays. The output relays are normally energized output

relays. The output relay for under frequency is activated at

frequencies higher than the preset value, while the output

relay for over frequency is activated at frequencies lower

than the preset value. This means that both output relays are

activated at frequencies within the interval between the under

and over frequency scale range.

OrderinG number

TerminalS

1-3

2-3

T3000.0010

230 V

T3000.0020

450 V

400 V

T3000.0030

110 V

100 V

T3000.0040

480 V

415 V

T3000.0050

127 V

120 V

Ordering Information

Simplified Circuit Diagram

Features & Benefits

Other voltages are available on request.

Specifications

Overfrequency Level 45-65 Hz

Delay

1-10 sec.

Underfrequency Level 45-65 Hz

Delay

1-10 sec.

Max. Voltage

660 V

Voltage Range

70-110%

Consumption

5 VA at U

N

Continuous Current

2 x I

N

Frequency Range

40-70 Hz

Output Relay

Normally energized

Contact Rating

AC: 250 V, 2 A, 250 VA; DC: 60 V, 2 A, 100 W

Overall Accuracy

±3% of highest value

Repeatability

±1%

Operating Temperature –20°C to + 70°C

Dielectric Test

2500 V, 50 Hz

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

10

9

8

7
6
5

L

1

(L)

L

2

(N)

OVERFREQUENCY

ALARM

UNDERFREQUENCY

ALARM

T3000

(Frequency Relay)

2

3

1

FeaTureS

beneFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of power,

pick-up, and output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply (up

to 690 Vac)

Simplifies design and installation.

No need for PTs.

Combining 2 relays in

same enclosure

Economic solution . Monitoring both

underfrequency and overfrequency in same unit,

and occupying less space in the switch panel

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

Rev: 4-A-050213

Advertising