GE Industrial Solutions EntelliGuard G Drawout Secondary Disconnect User Manual
Entelliguard
 
Introduction 
Drawout Secondary Disconnect: 
Drawout breakers are always supplied with one 
secondary disconnect (auxiliary connection block) 
suitable for 39 connection points (terminal A). 
When the number of factory installed accessories 
exceeds the available number of connection 
points needed, a 2
nd
connection block is
automatically added (terminal B) to the Breaker. 
For cases where the accessories are mounted in 
the field, or needed for the cassette an additional 
auxiliary connection block can be added to 
provide 39 more additional connections. 
 
Figure 1. SD Breaker End
Figure 2. SD Cassette End
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Catalog Number: 
 
 Catalog No Description 
 GSDWTR 
 Aux, Disconnect Drawout 39 
terminal 
 
Use the following procedure to install the 
Drawout Secondary Disconnect accessory into 
the circuit breaker. 
 
Installation of Breaker side Secondary 
disconnect: 
 
1. Turn the breaker off and discharge the closing 
springs by depressing the OFF and ON buttons in 
the sequence OFF-ON-OFF. Verify that the 
breaker OFF-ON indicator shows OFF on a green 
background and that the charge indicator shows 
DISCHARGE on a white background. If installing 
in a draw-out type breaker remove breaker from 
adaptor (cassette) before continuing.
2. The breaker should be safely isolated and fully 
removed from the cassette. 
 
3. Place the secondary disconnect block on the 
mounting bracket and assemble the two 
mounting screws as shown in fig 3 & 4
.
EntelliGuard
®
G Circuit Breaker
Accessories 
 
 Drawout Secondary Disconnect 
WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,
and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation , et décharger les
resorts d’armement
DEH-41401 Installation Instructions
1