Incorrect alignment – Xylem 8200 Series Base Mounted Centrifugal Fire Pumps AC2675 REV.C User Manual

Page 10

Advertising
background image

ANSI/OSHA Coupling Guard Exploded View
For Typical 8200 Series Fire Pump Installation

INNER GUARD

OUTER GUARD

ATTACH SUPPORT BRACKET
TO BEARING HOUSING

SUPPORT
BRACKET

LOCATE SUPPORT ARM
BETWEEN OUTER GUARD ENDS.
ALIGN THE ARM WITH HOLES IN
THE OUTER GUARD AND HOLES
IN THE SADDLE BRACKET.

NUT

BRACKET SUPPORT
ATTACHED INSIDE HERE
IN LINE WITH BOLT

BRACKET
SUPPORT

LOCKWASHER

CAPSCREW

FLAT WASHER

SPACER WASHER

MOTOR SADDLE
BRACKET ATTACH
TO MOTOR SADDLE

THIS OPTION USED IN PLACE OF SPACER WHERE
OVERALL LENGTH OF GUARD EXCEEDS 12 INCHES
OR GUARD WITH IS OVER 10 INCHES ACROSS
THE FLATS.

Method 1 – Straight Edge Alignment for
Standard Sleeve Type Coupler with Black
Rubber Insert

10

(See Figure 7A)

Proceed with this method only if satisfied that
face and outside diameters of the coupling
halves are square and concentric with the
coupling borers. If this condition does not
exist or elastomeric couplings do not make
this method convenient, use Method 2.

1. Check angular misalignment using a

micrometer or caliper. Measure from the
outside of one flange to the outside of the
opposite flange at four points 90° apart.
DO NOT ROTATE COUPLER.
Misalignment up to 1/64" per inch of
coupler radius is permissible.

2. At four points 90° apart (DO NOT

ROTATE COUPLER), measure the
parallel coupler misalignment by laying a
straight edge across one coupler half and
measuring the gap between the straight
edge and opposite coupler half. Up to a
1/64" gap is permissible.

STRAIGHT EDGE

FEELER GAGE

ANGULAR ALIGNMENT

PARALLEL ALIGNMENT

INCORRECT ALIGNMENT

STRAIGHT EDGE

FEELER GAGE

CORRECT ALIGNMENT

FIGURE 7A – CHECKING ALIGNMENT

(METHOD 1)