Field

Display

Parameter

Definition

Range

Notes

Setting

ROOM DESIGN

The room design

35°F to 100°F

If the original heating system design

TEMP

temperature used

(1°C to 37°C)

criteria are unknown, the ROOM

in the original heat

DESIGN TEMP should be set to the

loss calculation for

estimated highest typical (non set-

the building

back) thermostat setting

OUTDOOR

The outdoor design

-60°F to +45F If the original heating system design

DESIGN TEMP

temperature used

(-51°C to 7°C) criteria are unknown, the OUTDOOR

in the original heat

DESIGN TEMP should be set to the

loss calculation for

estimated lowest expected outdoor

the building

temperature based on geographical
location

BOILER DESIGN

Supply water tem-

70°F to 210°F

Recommended Settings

TEMP

perature required

(21°C to 93°C) High Mass Radiant (e.g., concrete):

to heat the building

120°F (49°C)

when outdoor

Low Mass Radiant (e.g., wood floor):

temperature is equal

140°F (60°C)

OUTDOOR DESIGN

Fancoil: 190°F (88°C)

TEMP

Fin Tube Convector: 180°F (82°C)
Radiator: 160°F (71°C)
Baseboard: 150°F (66°C)

BOILER

Minimum water

OFF

Recommended Settings

MINIMUM

temperature to be

80°F to 180°F

Cast iron boiler: 150°F

TEMP

returned to boiler

(27°C to 82°C) Copper tube boiler: 140°F

Condensing boiler: OFF
Electric boiler: OFF
Note: Refer to boiler installation
instructions to determine the minimum
allowable return temperature

BOILER

The range of tem-

ADJ

The controller calculates a boiler

DIFFERENTIAL

perature deviation

2°F to 42°F

target temperature based on

TEMP

allowed above and

(1°C to 23°C)

multiple variables. The BOILER

below boiler target

DIFFERENTIAL TEMP is the range

temperature

around the target temp in which the
supply temperature is allowed to float.
For example, with a target temperature
of 150°F and a BOILER DIFFERENTIAL
TEMP of 10°F, the supply temp will vary
between 145° and 155°F. Using the
Auto Differential (ADJ) setting is recom-
mended for optimum performance

WARM

Outdoor tempera-

35°F to 100°F

When the outdoor temperature exceeds

WEATHER

ture above which

(1°C to 37°C)

the WWSD setting, the controller will not

SHUTDOWN

the controller will

OFF

enable the boiler. It is typical to set the

TEMP

not activate the

WWSD value equal to the ROOM

boiler

DESIGN TEMP. The OFF setting defeats
the WWSD logic

ENGLISH/

Parameters to be

°F or °C

METRIC

displayed in
Farenheit or
Celsius

ESCAPE

Exit set up menu

To escape the set up menu, press either
the

or

key