Boiler reset control set-up parameters – Bell & Gossett 210668B Z-4M User Manual
Page 3

Field
Display
Parameter
Definition
Range
Notes
Setting
ROOM DESIGN
The room design
35°F to 100°F
If the original heating system design
TEMP
temperature used
(1°C to 37°C)
criteria are unknown, the ROOM
in the original heat
DESIGN TEMP should be set to the
loss calculation for
estimated highest typical (non set-
the building
back) thermostat setting
OUTDOOR
The outdoor design
-60°F to +45F If the original heating system design
DESIGN TEMP
temperature used
(-51°C to 7°C) criteria are unknown, the OUTDOOR
in the original heat
DESIGN TEMP should be set to the
loss calculation for
estimated lowest expected outdoor
the building
temperature based on geographical
location
BOILER DESIGN
Supply water tem-
70°F to 210°F
Recommended Settings
TEMP
perature required
(21°C to 93°C) High Mass Radiant (e.g., concrete):
to heat the building
120°F (49°C)
when outdoor
Low Mass Radiant (e.g., wood floor):
temperature is equal
140°F (60°C)
OUTDOOR DESIGN
Fancoil: 190°F (88°C)
TEMP
Fin Tube Convector: 180°F (82°C)
Radiator: 160°F (71°C)
Baseboard: 150°F (66°C)
BOILER
Minimum water
OFF
Recommended Settings
MINIMUM
temperature to be
80°F to 180°F
Cast iron boiler: 150°F
TEMP
returned to boiler
(27°C to 82°C) Copper tube boiler: 140°F
Condensing boiler: OFF
Electric boiler: OFF
Note: Refer to boiler installation
instructions to determine the minimum
allowable return temperature
BOILER
The range of tem-
ADJ
The controller calculates a boiler
DIFFERENTIAL
perature deviation
2°F to 42°F
target temperature based on
TEMP
allowed above and
(1°C to 23°C)
multiple variables. The BOILER
below boiler target
DIFFERENTIAL TEMP is the range
temperature
around the target temp in which the
supply temperature is allowed to float.
For example, with a target temperature
of 150°F and a BOILER DIFFERENTIAL
TEMP of 10°F, the supply temp will vary
between 145° and 155°F. Using the
Auto Differential (ADJ) setting is recom-
mended for optimum performance
WARM
Outdoor tempera-
35°F to 100°F
When the outdoor temperature exceeds
WEATHER
ture above which
(1°C to 37°C)
the WWSD setting, the controller will not
SHUTDOWN
the controller will
OFF
enable the boiler. It is typical to set the
TEMP
not activate the
WWSD value equal to the ROOM
boiler
DESIGN TEMP. The OFF setting defeats
the WWSD logic
ENGLISH/
Parameters to be
°F or °C
METRIC
displayed in
Farenheit or
Celsius
ESCAPE
Exit set up menu
—
To escape the set up menu, press either
the
or
key