Bell & Gossett 193 TECHNOVAR VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED AJUSTABLE FREQUENCY DRIVE User Manual
Page 46

Operating Instruction
46
11.
SAVE ???
SAVED
appears on the display. After five
seconds the display jumps back to the
1
st
display.
These parameters can also be set during operation; To do so, briefly press the
button and repeat steps 1 – 10.
Please Note: often shown display
12.
INVERTER LOCKED
enable inverter
This message appears when the connection of
terminal X1/4-X1/5 is open (external release contact).
10 Settings at Secondary Menu
Important: Before entering the secondary menu these instructions must
be read carefully to prevent incorrect settings which will cause
malfunction.
Secondary Menu:
Stop motor by pressing OFF
INVERTER STOP
ON -> START
Press for 3 seconds to change to
PASSWORD
0000
Set ‘Password 0066’ by pressing
PASSWORD
0066
Confirm by pressing and the first
window of the sub menu is shown
J O G – MODE
0.0Hz X.XX psi
In the following paragraphs all possible settings are listed (in the display, there is
shown the European default setting).
10.1 JOG-MODE
Display and Manual Operation Mode
J O G – MODE
0.0Hz X.XX psi
Actual outgoing frequency and actual analog input are
shown. By pressing or in this menu, the
Note: The password must be entered at each entry