TO BOILER
FEED
SYSTEM

REDUCER

STRAINER

SERIES VLR DUPLEX

PIPING DIAGRAM

DRAIN

DRAIN

DRAIN

DV

PRIMING

OPENING

EQUALIZING LINE —

3

/

4

"

BOILER

FROM BOILER
FEED SYSTEM

— GATE VALVE

— DISCHARGE VALVE

DV

— STEAM OR PLUG COCK
— UNION

— CHECK VALVE

OPEN VENT ABOVE
BOILER WATER LINE

RETURN FROM
HEATING SYSTEM

Receivers ar

e non-code cast iron.

PRELIMINAR

Y INSPECTION

Assur

e that there is no shipping damage.

Assure that nameplate ratings agree with job specifications and
actual conditions.

HANDLING

Use car

e in installing unit.

LOCA

TION

Place unit for easy access to all parts. Allow adequate space

for servicing. Check ambient conditions.

NOTICE/TEMPERA

TURE LIMITS

Motors ar

e designed to operate in 104°F max. ambient.

Insulate or ventilate as required.

PIPING

(General)

Pipe the unit per the Elementary Piping Diagram. Locate and

support piping so as to not load the discharge valve.

PIPING (

Vent)

Install a vent pipe to atmospher

e. Pipe to be size of vent port

on unit. Do not restrict or reduce vent opening or exceed 20
inch vertical height unless an overflow connection is provided.

PRIMING POR

T

Pr

ovide a priming port as shown on piping diagram.

FLOA

T SWITCHES

Floats ar

e locked in place to prevent damage during shipment.

Remove shipping locks. Check factory settings. Floats are
adjustable for various levels of operation.

See page 7 for detailed instructions.

EQUALIZING LINE

An equalizing line must be installed with all Series VLR units.

This line must be installed to prevent formation of a vacuum on
the radiation side of the system when steam stops flowing in
the mains. This vacuum may be higher than return line vacuum,
which would prevent condensate from flowing back to pump.
To correct this in an unzoned system, install equalizer line as
shown in the piping diagram. To correct this in a zoned system,
install equalizer line for each zoned section or install a vacuum
breaker on supply line on radiation side of each zone control
valve.

3

CAUTION:

UNIT LIFTING EYE

Use unit lifting eyes only to lift unit as shipped fr

om

factory. Unit must be empty and disconnected from pipes,
anchors and other restraints. Use proper rigging pro-
cedures. Failure to follow these instructions could result in
injury or property damage.

CAUTION:

NOT A CHEMICAL PUMP

Inject boiler feed compounds fr

om chemical feed tank

into boiler feed piping – never into condensate tank. Failure
to follow these instructions could result in injury or property
damage.

EQUALIZING CONNECTIONS FOR ZONED SYSTEMS

ZONE CONTROL

VALVE

STEAM MAIN

M

TO ZONE

RETURN MAIN

FIG. 3.

WARNING: EXPLOSIBLE

Do not pr

essurize receiver. Isolate receiver during leak

test. Do not plug overflow. Do not restrict vent opening to
atmosphere. Open valves slowly. Failure to follow these
instructions could result in serious injury or death.

FIG. 4